Staff canteen kitchen design must solve ventilation and exhaust while keeping dining free of kitchen odor. How should it be designed?

Staff canteen kitchen ventilation design
1. Airflow: total exhaust = local hood exhaust + general exhaust. Hood flow follows hood size or appliances; general exhaust is calculated.
2. Zoning of exhaust
1) Separate staple and non-staple systems—different hours, different fumes, and different hoods (plain vs water-wash) that unbalance fans if mixed.
2) Keep each fan on as few hoods as possible (ideally ≤2) so volumes stay even, on/off is flexible, energy falls, and ducts/fans stay quieter and easier to install.
3) Place general exhaust inlets as far from hoods as practical, based on range layout.
4) Prefer centrifugal fans for static pressure; if inline/box fans are used, choose external-motor types.
3. Makeup air
Exhaust should exceed makeup so the kitchen is slightly negative and dining slightly positive—preventing odor transfer. Makeup about 80–90% of exhaust, with 30–40% delivered to dining; kitchen negative pressure generally ≤5 Pa. Direct supply over hood fronts for cooling and capture; other outlets in prep. Face velocity near 2 m height ideally <0.25 m/s. Keep makeup systems modest (often <4000 m³/h) with speed-controlled fans.
Design after the operator supplies process drawings. Use small dedicated exhausts, limit negative pressure, and in cold climates block first-floor door drafts—flexible and energy-saving.
Prev: Notes for School Kitchen Gas Retrofit
Next: 没有了!
Price transparency
Nationwide coverage
Rapid design
Quick quote
Worry-free after sale
Guangdong Jiushang Electronic Technology Co., Ltd.
+86-400-0622-168
Mobile: +86-135-2862-7820
Contact: Manager Liu
Address: Building 5, Huyue Bay Area, Humen Town, Dongguan City, Guangdong Province, China